HOVAL PLATE EXCHANGER SPECIFICATIONS

Configuration
Modify this module parameters
Delete this module
Modify the module's width

Operating Principle

Summer operation

In summer operation, heat from the outside fresh air is transferred to the outgoing air, greatly reducing air-conditioning costs.


Winter operation

In winter, heat from the outgoing air is recovered and transferred to the fresh incoming air, greatly contributing to reduced heating costs.

phe500_operating_principle
Configuration
Modify this module parameters
Delete this module
Modify the module's width

Dimensional Data

Dimension Sensible Plate
Model Square size (S)
(in/mm)
Diagonal (D)
(in/mm)
Height (H)
(in/mm)
60
23.62/600
32.64/829
As requested
70 27.56/700
38.19/970
As requested
85 33.46/850
46.54/1182
As requested
100 39.7/1000 54.88/1394 As requested
120
47.24/1200
66.02/1677 As requested
140
55.12/1400
77.17/1960
As requested
170
66.93/1700
93.86/2384
As requested
200

78.74/2000

110.55/2808
As requested
Configuration
Modify this module parameters
Delete this module
Modify the module's width

1. General specifications:

  • 1.1 Furnish and install the Hoval Series air-to-air plate exchanger as shown in the schedule, to be manufactured by Innergy tech inc., Drummondville, Quebec, Canada.
  • 1.2 The air-to-air plate exchanger shall transfer heat between outgoing and incoming air streams in cross flow arrangement.
  • 1.3 Performance data derived from laboratory testing on heat exchanger conditions is in accordance with ASHRAE Standard 84-1991 “method of testing air-to-air heat exchangers”. Performance shall be rated in with AHRI Standard 1060 (I-P) testing procedures.
  • 1.4 The sensible plate exchanger shall be listed in the AHRI Certified Product Directory.
  • 1.5 The sensible plate exchanger shall bear the AHRI Certified Product Seal.
  • 1.6 Sensible, latent and total effectiveness along with pressure drop, EATR and OACF rating shall be clearly documented with performance tests conducted in accordance with ASHRAE Standard 84-91 and AHRI Standard 1060 (I-P).
  • 1.7 Manufacturers of alternate equipment must be approved to bid via addendum, in writing by the specifying engineer, at least two weeks prior to bi time in order for their bid to be accepted by the contractor. If the equipment is not pre-approved then under no circumstances shall the contractor invest time or money in receiving submittals or considering the equipment. Costs associated with dimensional, performance, or other deviations from the specified equipment, including engineering costs to evaluate such deviations, shall be paid by the contractor.
  • 1.8 The air-to-air plate exchanger manufacturer must be ISO: 9001-2008 certified.
  • 1.9 The air-to-air plate exchanger manufacturer must have a least ten (10) years of experience in the manufacturing of energy recovery components.

2. Product specifications:

  • 2.1 The exchanger plates shall be 99.9% pure aluminum. Plates made from aluminum alloys, plastic, fiber, steel or other material(s) are unacceptable.
  • 2.2 The plates shall be die formed with the patented positive/negative dimple stamping that provides the Hoval Series exclusive plate profile and discontinuous channel design. Plate profiles of the laminar flow design type are unacceptable.
  • 2.3 Aluminum plate thickness shall be 0.005” (0.127 mm)
  • 2.4 The connecting plate edges shall be double folded. The double fold shall provide a six fold material thickness on the leading and trailing edges of the plate exchanger and provide protection from the cutting edge of the exchanger plates within the double fold. Construction methods that use a single fold, or glue at the leading and trailing edges of the exchanger are not acceptable.
  • 2.5 The air-to-air plate exchanger core shall be assembled into a strong, self-supporting frame made of aluminum corner extrusions and 20 gauge galvanized steel end plates.
  • 2.6 The corners of the assembled exchanger package and the inside of the double folded seams shall be sealed with synthetic casting resin per patented method.
  • 2.7 The aluminum corner extrusions shall be hollow to accept mounting screws and shall provide a 45° corner support angle
  • 2.8 The Hoval “V Series construction (standard product): The air-to-air plate exchanger package with synthetic resin sealed corners shall be resistant to temperatures up to 194°F (90°C).
  • 2.9 The Hoval “G Series construction option: The air-to-air plate exchanger plates shall have a PVC mill applied coating. The extrusions, endplates and all sheet metal surfaces are to be epoxy coated, providing protection for installations in corrosive environments. The heat exchanger package with synthetic resin sealed corners is to be resistant to temperatures up to 194°F (90°C).
  • 2.10 The Hoval “T Series construction option: The air-to-air plate heat exchanger shall be of High-Temperature construction. The plate exchanger shall be sealed with a special high temperature resistant sealant to protect the heat exchanger package against temperatures in the air streams of up to 392°F (200°C).
  • 2.11 The air-to-air plate exchanger shall withstand, without significant change in its performances and pressure drops, a pressure differential of at least 6 w.g.. It shall withstand a pressure differential of 10 w.g. without permanent deformation.

Configuration
Modify this module parameters
Delete this module
Modify the module's width
Download
Configuration
Modify this module parameters
Delete this module
Modify the module's width
Configuration
Modify this module parameters
Delete this module
Modify the module's width
Other Product
Configuration
Modify this module parameters
Delete this module
Modify the module's width
Sensible Plate Exchanger
AHE500

The best cost effective solution to heat recovery
Learn more
Sensible Plate Exchanger
Hoval

The best cost effective solution to heat recovery
Learn more